Fused Quick disconnected type kit for low voltage copper or aluminum conductor cables. Recommended for street, highway, and flood lighting in outdoor locations in both wet or dry areas. The model SEC 1791-DF connector kit was specially designed to fuse a complete circuit. SEC connector kits are designed to splice up to four conductors from number 10 to 2/0 stranded on the line side and from number 12 to 4 stranded or solid on the load side. Conductors can be removed and reinstalled. Any standard midget, ferrule type fuse (except glass tube) may be used in this connector kit. Fuse dimensions are 13/32” diameter by 1-1/2” length. SEC fused connectors are designed for 600 volts or less. | |||||||||||||||||||
|
|||||||||||||||||||
|
Required Torque Inch Pounds
CAT NO. | WIRE SIZE | WIRE TYPE | WIRE DIA RANGE (IN) |
CUTTING RANGE NO. |
TORQUE (IN-LBS) |
SEC 1791-DF-5, 0791-1 | 8 | RHH, RHW-2, THW, TW, USE-2, XHHW | 15/64 | 1 | 100 |
6 | RHH, RHW-2, THHN, THW, THWN, USE-2, XHHW-2 | 19/64 | 1 | 115 | |
4 | THHN, THW, THWN | 5/16 | 1 | 115 | |
4 | RHH, RHW-2, USE-2, XHHW-2 | 23/64 | 2 | 115 | |
3 | THHN, THWN | 11/32 | 2 | 120 | |
3 | THW | 3/8 | 2 | 120 | |
2 | RHH, RHW-2, THHN, THW, THWN, USE-2, XHHW-2 | 13/32 | 2 | 120 |
CAT NO. | WIRE SIZE | WIRE TYPE | WIRE DIA RANGE (IN) |
CUTTING RANGE NO. |
TORQUE (IN-LBS) |
SEC 1791-DF-5. 0791-1 | 1 | THWN, THHN, XHHW-2 | 7/16 | 2 | 120 |
1 | USE-2, RHW, RHH, THW | 31/64 | 3 | 120 | |
1/0 | USE-2, RHW-2, RHH, THWN, THNN, THW, XHHW-2 | 17/32 | 3 | 120 | |
2/0 | USE-2, RHW-2, RHH, THWN, THNN, THW, XHHW-2 | 37/64 | 3 | 120 | |
SEC 1791-DPS-1 1791-DS-3 | 8 | RHH, RHW-2, THW, TW, USE-2, XHHW | 15/64 | 1 | 60 |
6 | RHH, RHW-2, THHN, THW, THWN, USE-2, XHHW-2 | 19/64 | 1 | 60 | |
4 | THHN THW, THWN | 5/16 | 1 | 60 | |
4 | RHH, RHW-2, USE-2, XHHW-2 | 23/64 | 2 | 60 |
Ordering Instructions
The same kit will fit most conductor sizes from number 10 to 2/0 on line side and number 12 to 4 on load side either copper or aluminum, stranded wire. One kit will splice four conductors on line side and provided double fusing for load side.
Patent No. 3,874,760