SEC Splice Box
Click here for a printable PDF version of this page | |||||||||||||
Model SEC 0791-0
|
|||||||||||||
For Copper or Aluminum Stranded Wire |
|||||||||||||
Four-way semi permanent connector splice box for low voltage copper or aluminum conductor cables. Recommended for street, highway, and flood lighting in outdoor locations in both wet or dry areas. SEC splice boxes are designed to fit most conductors from number 10 to 2/0, depending on insulation thickness, and will provide connections for up to four wires or any combination. Conductors are attached with simple screw lugs for easy, quick insulation, Conductors can be easily removed and reinstalled. | |||||||||||||
|
|||||||||||||
|
Required Torque Inch Pounds
CAT NO. | WIRE SIZE | WIRE TYPE | WIRE DIA RANGE (IN) |
CUTTING RANGE NO. |
TORQUE (IN-LBS) |
SEC 0791-1 0791-3 | 8 | RHH, RHW-2, THW, TW, USE-2, XHHW | 15/64 | 1 | 75 |
6 | RHH, RHW-2, THHN, THW, THWN, USE-2, XHHW-2 | 19/64 | 1 | 110 | |
4 | THHN, THW, THWN | 5/16 | 1 | 110 | |
4 | RHH, RHW-2, USE-2, XHHW-2 | 23/64 | 2 | 110 | |
3 | THHN, THWN | 11/32 | 2 | 120 | |
3 | THW | 3/8 | 2 | 120 |
CAT NO. | WIRE SIZE | WIRE TYPE | WIRE DIA RANGE (IN) |
CUTTING RANGE NO. |
TORQUE (IN-LBS) |
SEC 0791-1 0791-3 | 2 | RHH, RHW-2, THHN, THW, THWN, USE-2, XHHW-2 | 13/32 | 2 | 150 |
1 | THWN, THHN, XHHW-2 | 7/16 | 2 | 150 | |
1 | USE-2, RHW, RHH, THW | 31/64 | 2 | 150 | |
1/0 | USE-2, RHW-2, RHH, THWN, THNN, THW, XHHW-2 | 17/32 | 3 | 180 | |
2/0 | USE-2, RHW-2, RHH, THWN, THNN, THW, XHHW-2 | 37/64 | 3 | 180 |
Ordering Instructions
Outside dimensions of conductors (including insulation) should be 5/64” larger than segment size. The same SEC connector splice box will fit conductions with outside dimensions from 9/32” to 3/4″
Patent No. 3,874,760