Model SEC 0791-0

 

For Copper or Aluminum Stranded Wire

Four-way semi permanent connector splice box for low voltage copper or aluminum conductor cables. Recommended for street, highway, and flood lighting in outdoor locations in both wet or dry areas. SEC splice boxes are designed to fit most conductors from number 10 to 2/0, depending on insulation thickness, and will provide connections for up to four wires or any combination. Conductors are attached with simple screw lugs for easy, quick insulation, Conductors can be easily removed and reinstalled.
Splice Box Complete

Splice Box Complete

Parts Lists
SEC 0791-0 Splice Box Complete
SEC 0791-1 Splice Box Body
SEC 0791-2 Splice Box Cap
SEC 0791-3 Splice Box Lux Assembly

Listed
Splice Box
9D70

Required Torque Inch Pounds

CAT NO. WIRE SIZE WIRE TYPE WIRE DIA
RANGE (IN)
CUTTING
RANGE NO.
TORQUE
(IN-LBS)
SEC 0791-1 0791-3 8 RHH, RHW-2, THW, TW, USE-2, XHHW 15/64 1 75
6 RHH, RHW-2, THHN, THW, THWN, USE-2, XHHW-2 19/64 1 110
4 THHN, THW, THWN 5/16 1 110
4 RHH, RHW-2, USE-2, XHHW-2 23/64 2 110
3 THHN, THWN 11/32 2 120
3 THW 3/8 2 120
CAT NO. WIRE SIZE WIRE TYPE WIRE DIA
RANGE (IN)
CUTTING
RANGE NO.
TORQUE
(IN-LBS)
SEC 0791-1 0791-3 2 RHH, RHW-2, THHN, THW, THWN, USE-2, XHHW-2 13/32 2 150
1 THWN, THHN, XHHW-2 7/16 2 150
1 USE-2, RHW, RHH, THW 31/64 2 150
1/0 USE-2, RHW-2, RHH, THWN, THNN, THW, XHHW-2 17/32 3 180
2/0 USE-2, RHW-2, RHH, THWN, THNN, THW, XHHW-2 37/64 3 180